GPR-24 (12) kV Series Oruka Main Unit Switchgear
Lakotan
GPR-24 jara Oruka Akọkọ Unit jẹ ẹya extensible, SF6 ya sọtọ switchgear, pẹlu ti won won foliteji ti 12&24 kV.Gbogbo awọn ẹya ifiwe HV rẹ wa ninu ojò gaasi ti afẹfẹ, eyiti a ṣe lati irin alagbara ti 3mm.Gbogbo apejọ iyipada jẹ SF6 ti ya sọtọ, ati ni ominira lati eyikeyi ipa ita, ni idaniloju pe igbẹkẹle nla ti iṣẹ ati itọju ọfẹ.Nipa plug-in iru busbar itẹsiwaju, GPR-24 jara Oruka akọkọ Unit le jẹ ti apapo free ati ki o kikun modularization.Ifaagun busbar ti kọja iru idanwo fun agbara ati iduroṣinṣin igbona, ati pe o jẹ idabobo ni kikun ati aabo, ti n ṣafihan igbẹkẹle giga ati ailewu.GPR-24 jara Iwọn Main Unit jẹ o dara fun gbogbo nẹtiwọọki MV to 24 kV, gbogbo awọn ibudo agbara iwapọ, awọn ipinpinpin agbara ni gbogbo awọn ile-iṣẹ pataki, gẹgẹbi ile-iṣẹ epo-kemikali, awọn ile-iṣẹ irin ati awọn ile-iṣẹ iwakusa, ati gbogbo awọn ile-iṣẹ iyipada ati agbara afẹfẹ. eto.
Awọn ẹya ara ẹrọ
1. Ilana ilana ilọsiwaju fun ojò gaasi
Ige laser ti iṣakoso oni-nọmba ati eto punching ati iwọn-mẹta ati eto alurinmorin laser marun-aksi ti a gbe wọle lati Germany pẹlu rii daju wiwọ gaasi ati isokan ti gbogbo awọn tanki gaasi.
Eto wiwa wiwa helium ni kikun ati isọdọkan, ti a ṣe nipasẹ SEILER Vakuumtechnik GmbH, nipasẹ wiwa jijo Helium nipasẹ iwoye titobi, mu iwọn jijo gaasi wa fun ọdun kan si kere ju 0.02%, ni idaniloju igbesi aye ojò gaasi ti o ju ọdun 30 lọ.
Ilana ilana ilọsiwaju fun awọn ẹya.
Gbogbo awọn ẹya idayatọ resini iposii, pẹlu awọn ọpá ti o ya sọtọ, jẹ iṣelọpọ nipasẹ adaṣe ni kikun ati oni nọmba iṣakoso iposii resini igbale dapọ/titẹ gelatinizing eto lati Hedrich (Germany).
Asopọmọra busbar, asopo okun, ohun elo ipari ati awọn ẹya miiran ti a fi sọtọ roba silikoni jẹ iṣelọpọ nipasẹ adaṣe ni kikun-laifọwọyi ati iṣakoso oni-nọmba silikoni ti o dapọ roba / titẹ gelatinizing eto lati VOGEL (Switzerland).
2. Awọn solusan ti o dara julọ fun awọn ọja
Pẹlu ọna kekere ati iwapọ, awọn ẹka iṣẹ ipilẹ K, T, V, B ati C ni iwọn aṣọ: 350 * 800 * 1380 mm (iwọn * ijinle * giga) .
Awọn ojutu pipe:
Ẹya ẹyọkan: ẹyọ fifọ fifuye, ẹyọ-fiusi, ẹyọ fifọ Circuit igbale, ẹyọ apakan apakan busbar, ẹyọ okun, ẹyọ iwọn, abbl.
Àkọsílẹ version le ti wa ni ṣe soke ti meji, mẹta, mẹrin, marun tabi mẹfa iṣẹ-ṣiṣe sipo.
Awọn ẹya ẹyọkan ati ẹya idinamọ le jẹ asopọ nipasẹ awọn asopọ busbar ni irọrun.
3. Strong adaptability si awọn ayika
Eto adaṣe akọkọ ti ni edidi ni kikun ninu ojò gaasi SF6 ati pe kii yoo ni ipa nipasẹ agbegbe ita, ominira ti ipa ti ìri, eruku, kurukuru iyo, bbl Nitorina, GPR-24 jara le ṣee lo ni ọpọlọpọ awọn ipo iṣẹ ti o lagbara. .
12kV Imọ Data
Apejuwe | Ẹyọ | Ẹka LBS | Yipada-fiusi kuro | Ẹka VCB | Busbar apa apakan | |
Foliteji won won | kV | 12 | 12 | 12 | 12 | |
Igbohunsafẹfẹ agbara agbara (iṣẹju 1) | Ipele to alakoso / aye | kV | 42 | 42 | 42 | 42 |
Kọja ijinna ipinya | kV | 48 | 48 | 48 | 48 | |
Impulse withstand foliteji | Ipele to alakoso / aye | kV | 75, (95)* | 75, (95)* | 75, (95)* | 75, (95)* |
Kọja ijinna ipinya | kV | 85, (110)* | 85, (110)* | 85, (110)* | 85, (110)* | |
Iwọn igbohunsafẹfẹ | Hz | 50,60 | 50,60 | 50,60 | 50,60 | |
Ti won won lọwọlọwọ | A | 630 | ① | 630 | 630 | |
Ti won won kukuru Circuit fifọ lọwọlọwọ | kA |
| ② | 20, (25)* |
| |
Ti won won kukuru akoko withstand lọwọlọwọ | kA/s | 20/3, (20/4, 25/1)* |
| 20/3, (20/4, 25/3)* | 20/3, (20/4, 25/1)* | |
Ti won won tente oke withstand lọwọlọwọ | kA | 50, (63)* |
| 50, (63)* | 50, (63)* | |
Ti won won kukuru Circuit ṣiṣe lọwọlọwọ | kA | 50, (63)* | ② | 50, (63)* | 50, (63)* | |
Iwọn gbigbe lọwọlọwọ | A |
| 1800 |
|
| |
Ti won won lọwọ fifuye kikan lọwọlọwọ | A | 630 |
|
| 630 | |
Ti won won titi lupu kikan lọwọlọwọ | A | 630 |
|
| 630 | |
5% ti nṣiṣe lọwọ fifuye fifọ lọwọlọwọ | A | 31.5 |
|
| 31.5 | |
Ti won won awọn ọna ọna |
|
|
| Eyin-0.3s-CO-180-CO |
| |
Mechanical s'aiye | Ops. | 5000 | 5000 | 10000 | 5000 | |
Itanna s'aiye |
| E3 |
| E2 | E3 | |
Sisanra ti irin alagbara, irin | mm | 3.0 | ||||
Oṣuwọn SF6titẹ | kPa | 30 (ni 20℃, 101.3kPa) | ||||
Oṣuwọn jijo ọdọọdun | 0.02% | |||||
Idanwo itọju omi | 12kV 24 wakati (ni 30 kPa labẹ omi) | |||||
Ti abẹnu aaki igbeyewo | 20kA 1s | |||||
Idaabobo ìyí | Gaasi ojò | IP 67 | ||||
Dimu fiusi | IP 67 | |||||
GPR apade |
| IP4X |
24kV Imọ Data
Apejuwe | Ẹyọ | Ẹka LBS | Yipada-fiusi kuro | Ẹka VCB | Busbar apa apakan | |
Foliteji won won | kV | 24 | 24 | 24 | 24 | |
Igbohunsafẹfẹ agbara agbara (iṣẹju 1) | Ipele to alakoso / aye | kV | 50, (65)* | 50, (65)* | 50, (65)* | 50, (65)* |
Kọja ijinna ipinya | kV | 64, (79)* | 64, (79)* | 64, (79)* | 64, (79)* | |
Impulse withstand foliteji | Ipele to alakoso / aye | kV | 95, (125)* | 95, (125)* | 95, (125)* | 95, (125)* |
Kọja ijinna ipinya | kV | 110, (145)* | 110, (145)* | 110, (145)* | 110, (145)* | |
Iwọn igbohunsafẹfẹ | Hz | 50, 60 | 50, 60 | 50, 60 | 50, 60 | |
Ti won won lọwọlọwọ | A | 630 | ① | 630 | 630 | |
Ti won won kukuru Circuit fifọ lọwọlọwọ | kA |
| ② | 20 |
| |
Ti won won kukuru akoko withstand lọwọlọwọ | kA/s | 20/3, (20/4)* |
| 20/3, (20/4)* | 20/3, (20/4)* | |
Ti won won tente oke withstand lọwọlọwọ | kA | 50 |
| 50 | 50 | |
Ti won won kukuru Circuit ṣiṣe lọwọlọwọ | kA | 50 | ② | 50 | 50 | |
Iwọn gbigbe lọwọlọwọ | A |
| 1400 |
|
| |
Ti won won lọwọ fifuye kikan lọwọlọwọ | A | 630 |
|
| 630 | |
Ti won won titi lupu kikan lọwọlọwọ | A | 630 |
|
| 630 | |
5% ti nṣiṣe lọwọ fifuye fifọ lọwọlọwọ | A | 31.5 |
|
| 31.5 | |
Ti won won awọn ọna ọna |
|
|
| Eyin-0.3s-CO-180-CO |
| |
Mechanical s'aiye | Ops. | 5000 | 5000 | 10000 | 5000 | |
Itanna s'aiye |
| E3 |
| E2 | E3 | |
Sisanra ti irin alagbara, irin | mm | 3.0 | ||||
Ti won won SF6 titẹ | kPa | 30 (ni 20℃, 101.3kPa) | ||||
Oṣuwọn jijo ọdọọdun | 0.02% | |||||
Idanwo itọju omi | 24kV 24 wakati (ni 30 kPa labẹ omi) | |||||
Ti abẹnu aaki igbeyewo | 20kA 1s | |||||
Idaabobo ìyí | Gaasi ojò | IP 67 | ||||
Dimu fiusi | IP 67 | |||||
GPR apade | IP4X |
Awọn akọsilẹ:
① Ipin lọwọlọwọ ti ẹyọ-fiusi da lori idiyele ti fiusi: ≤100A
② Iyatọ kukuru kukuru fifọ / ṣiṣe lọwọlọwọ ti ẹyọ fiusi yipada da lori idiyele ti fiusi
* Awọn iye ni awọn biraketi wa fun awọn ibeere pataki, jọwọ kan si olupese tabi olupese fun alaye diẹ sii
GPR24 Series Akopọ
1. Nikan ojò iru
Akiyesi:
1. Awọn iye ni awọn biraketi ti a samisi pẹlu "*" jẹ awọn ọja ni 24kV, agbara igbohunsafẹfẹ duro foliteji ti 65 / 79kV;
2. Ti o ba wa ọpọlọpọ awọn ohun elo Atẹle pupọ ninu iṣeto ni, afikun afikun fun wọn le fi sori ẹrọ lori oke ti nronu, giga rẹ jẹ 400mm.
2. GPR24 Àkọsílẹ iru-1 fun 12kV & 24kV (igbohunsafẹfẹ agbara withstand foliteji: 50/64kV)
Awọn akọsilẹ:
Ti ọpọlọpọ awọn paati Atẹle ba wa ninu iṣeto ni, apakan afikun fun wọn le fi sii lori oke GPR, giga rẹ jẹ 400mm